Rockwell Automation 1336 8A-48A Fiber Industry User Manual

Page 97

Advertising
background image

5–31

Programming

[Aux Input Select]

This parameter programs the action that occurs
when the “Auxiliary“ input is opened (low) and the
drive is running.

One of the following 5 actions may be selected:

0 Status only, no action. The drive continues to run,

but a status bit is available through remote I/O
communications to the programmable controller.

1 Drive continues to run, report status bit is sent to

the programmable controller and indicates alarm
status through the alarm contact CR4. Alarm will
be issued when TB2-16 & 17 opens and TB2-17
& 18 closes.

2 Drive ramps-to-stop, report status bit is sent to the

programmable controller and indicates fault status
through the fault contact CR3. When the input is
low (0), the drive will do a programmed ramp-to-
stop and display “Auxiliary Fault.”

3 Drive will coast-to-stop, report status bit is sent to

programmable controller and fault status is indi-
cated through fault contact CR3. When the input
is low (0), the drive will coast-to-stop and display
“Auxiliary Fault.”

4 DC injection brake-to-stop. Report status bit is

sent to the programmable controller and fault sta-
tus is indicated through the fault contact CR3.
When the input is low (0), the drive will brake-to-
stop using the value programmed for [DC Hold
Time] and [DC Hold Level]. During the hold time,
the drive cannot be reset or restarted until the
hold time is complete.

Parameter Number

174

Parameter Type

Read and Write

Factory Default

“0”

Units

Display Drive

“0” 0

Status Only

“1” 1

Alarm

“2” 2

Fault/Ramp

“3” 3

Fault/Coast

“4” 4

Fault/Brake

Faults