background image

2–26

Installation/Wiring

Figure 2.6 b
Option L5/L5E Wiring

Typical

TB3

A

A

ENC
RET

ENC
12V

Common

+24V

Typical

12V

681

100

90.9

5V

JP4

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

0.22

µ

f

1k

20k

510

510

510

User Supplied

24V AC/DC

Contacts shown are general, refer to Figure 2.5 for

Input Mode selection and recommended contact types.

Option L5/L5E – 24V AC/DC Interface Board Requirements

Circuits used with Option L5/L5E must be capable of operating with
high = true logic.

DC external circuits in the low state must generate a voltage of no
more than 8V DC. Leakage current must be less than 1.5 mA into a
2.5k ohm load.

AC external circuits in the low state must generate a voltage of no
more than 10V AC. Leakage current must be less than 2.5 mA into a
2.5k ohm load.

Both AC and DC external circuits in the high state must generate a
voltage of +20 to +26 volts and source a current of approximately 10
mA for each input. The L5/L5E option is compatible with these
Allen-Bradley PLC modules:

1771-OB

1771-OQ16

1771-OB16

1771-OBD

1771-OYL

1771-OBN

1771-OZL

1771-OQ

1771-OBB