3–5

Human Interface Module

Figure 3.4
Status Display

From this display, pressing any one of the 5 Display Panel keys will
cause “Choose Mode” to be displayed. Pressing the Increment or
Decrement keys will allow different modes to be selected as
described below and shown in Figure 3.5. Refer to the pages that
follow for operation examples.

Display
When selected, the Display mode allows any of the parameters to be
viewed. However, parameter modifications are not allowed.

Process
The Process mode displays two user-selected parameters with text
and scaling programmed by the user. Refer to Chapter 5 for further
information.

Program
Program mode provides access to the complete listing of parameters
available for programming. Refer to Chapter 5 for further parameter
programming information.

EEProm
This mode allows all parameters to be reset to the factory default
settings. In addition, a Series B HIM will allow parameter
upload/download between the HIM and drive.

Search (Series A, version 3.0 or Series B HIM Only)
This mode will search for parameters that are not at their default values.

Control Status (Series A, version 3.0 or Series B HIM Only)
Permits the drive logic mask to be disabled/enabled allowing HIM
removal while drive power is applied. Disabling the logic mask with a
Series A HIM below version 3.0 can be accomplished with [Logic
Mask] as explained on page 3–15. This menu also provides access to a
fault queue which will list the last four faults that have occurred. “Trip”
displayed with a fault indicates the actual fault that tripped the drive. A
clear function clears the queue – it will not clear an active fault.

Password
The Password mode protects the drive parameters against program-
ming changes by unauthorized personnel. When a password has been
assigned, access to the Program/EEProm modes and the Control
Logic/Clear Fault Queue menus can only be gained when the correct
password has been entered. The password can be any five digit num-
ber between 00000 and 65535. Refer to the example on page 3–13.