Rockwell Automation 1336 8A-48A Fiber Industry User Manual

Page 85

Advertising
background image

5–19

Programming

[Skip Freq 1-3]

These values, in conjunction with [Skip Freq Band],
create a range of frequencies at which the drive will
not continuously operate.

Parameter Number(s)

32-34

Parameter Type

Read and Write

Display Units / Drive Units

1 Hertz / Hertz

Factory Default

400 Hz

Minimum Value

0 Hz

Maximum Value

400 Hz

[Skip Freq Band]

This parameter determines the band width around a
[Skip Frequency]. The actual band width is
2 x [Skip Freq Band] –– 1/2 the band above and 1/2
the band below the skip frequency.

Parameter Number

35

Parameter Type

Read and Write

Display Units / Drive Units

1 Hertz / Hertz

Factory Default

0 Hz

Minimum Value

0 Hz

Maximum Value

15 Hz

Skip Frequency Band

e

vi

r

D

y

c

n

e

u

q

e

r

F

l

a

u

t

c

A

Frequency

Time

Skip Frequency

Command
Frequency

Skip Band

[Pulse/Enc Scale]

This parameter contains the scaling factor for both
pulse train inputs (TB2-7, 8) and encoder feedback
speed regulation (TB3 terminals 31-36).

1. Encoder Feedback Operation

Enter actual encoder pulses per revolution

2. Pulse Train Input

Scale

Factor

Incoming Pulse Rate (Hz)

Desired Command Freq.

Motor Poles

2

x

=

Parameter Number

46

Parameter Type

Read and Write

Display Units / Drive Units

Factor / Pulses per Rev

Factory Default

64 PPR

Minimum Value

1

Maximum Value

4096

Pulse Train Example:
4 Pole Motor, 60 Hz = Max. Speed.
The 1336–MOD–N1 option outputs 64 Hz/Hz.
At full analog reference, the pulse output will
be 60 Hz x 64 Hz/Hz = 3840 pulses/sec.

Pulse/Enc Scale

3840 Hz

60 Hz

4 Poles

2

= 128

This value will create a command frequency of
60 Hz for full analog reference to the option.

=

x

[Speed Filter]

A digital filter that sets the time constant for a single
pole speed command filter. This filter is located after
the active speed source is selected and before skip
speeds are checked.

Parameter Number

175

Parameter Type

Read and Write

Display Units / Drive Units

NA / NA

Factory Default

10

Minimum Value

1

Maximum Value

100

[Analog Filter]

An analog filter that sets the time command for the
single pole analog speed input filter. The pot,
isolated mA, 4-20 mA and 0-10 volt inputs are
filtered.

Parameter Number

176

Parameter Type

Read and Write

Display Units / Units

NA / NA

Factory Default

20

Minimum Value

1

Maximum Value

100

Frequency Set