Rockwell Automation 1336 8A-48A Fiber Industry User Manual

Page 36

Advertising
background image

2–28

Installation/Wiring

The interface board is jumper selectable to accept a 5V TTL or 12V
DC square-wave with a minimum high state voltage of 3.0V DC
(TTL) or 7.0V DC (12 volt encoder). Maximum low state voltage is
0.4V DC. Recommended wire – shielded, 0.750 mm

2

(18 AWG),

305 m (1000 ft.) or less. Maximum input frequency is 125kHz. See
Encoder & Communications Cabling on page 2–8.

Figure 2.6 d
Encoder Signal Wiring

31

Single-Ended, Dual-Channel

1

Differential

Single-Ended

Encoder Output

Connections

Differential

Encoder Output

Connections

32

33

34

35

36

A

B NOT

A NOT

B

31

TB3

32

33

34

35

36

to TE

A

B NOT

A NOT

B

TB3

to TE

to
Power Supply Common
(Terminal 36 or External)

1

For Single-Ended, Single-Channel (pulse) applications, eliminate the B and B (NOT) connections.
Some encoders may label the "A" connection as "Signal."

Important:

Correct direction of motor rotation as determined
during start-up (see Chapter 4) may require that the
A or B channel wiring be reversed.

Figure 2.6 e
Encoder Power Wiring

Common

+12V DC

(200 mA)

31

TB3

to TE

Internal

External

Encoder Power

Connections

using 12V DC Internal

(Drive) Power Source

Encoder Power

Connections using

External DC

Power Source

32

33

34

35

36

+

Common

External
Power
Supply

31

TB3

32

33

34

35

36

Important: Control Interface Board jumpers JP3 & JP4 must be set for the voltage level of the encoder output.

Minimum On Volts = 7V DC

Minimum Current = 10mA

Minimum On Volts = 3V DC

Minimum Current = 10mA

to TE