5–25

Programming

This group of parameters contains the programming options for digital and analog drive
outputs.

Output Config

[Digital Out Sel]

This parameter sets the condition that closes the
output contact at TB2 terminals 10 & 11.

Parameter Number

158

Parameter Type

Read and Write

Factory Default

“At Speed”

Units

Display Drive

“At Speed” 0

“At Frequency” 1

Requires value in [Dig Out Freq]

“At Current” 2

Requires value in [Dig Out Curr]

“At Torque” 3

Requires value in [Dig Out Torque]

[Dig Out Freq]

This value sets the trip point for the output contact at
TB2 terminals 10 & 11 when [Digital Out Sel] is set
to “At Frequency”. The contact will be closed when
above this value.

Parameter Number

159

Parameter Type

Read and Write

Display Units / Drive Units

0.01 Hertz / 32767 = Max Freq

Factory Default

0.00 Hz

Minimum Value

0.00 Hz

Maximum Value

Programmed [Maximum Freq]

[Dig Out Current]

This value sets the trip point for the output contact at
TB2 terminals 10 & 11 when [Digital Out Sel] is set
to “At Current”. The contact will be closed when
above this value.

Parameter Number

160

Parameter Type

Read and Write

Display Units / Drive Units

0% / 4096 = 100% of Drive Rated Amps

Factory Default

0 %

Minimum Value

0 %

Maximum Value

200 %

[Dig Out Torque]

This value sets the trip point for the output contact at
TB2 terminals 10 & 11 when [Digital Out Sel] is set
to “At Torque”. The contact will be closed when
above this value.

Parameter Number

161

Parameter Type

Read and Write

Display Units / Drive Units

0.1 Amps / 4096 = Rated Torque Amps

Factory Default

0.0 Amps

Minimum Value

0.0 Amps

Maximum Value

200% of [Rated Amps]

[Analog Out Sel]

This parameter selects the source that will drive the
analog output.

Parameter Number

25

Parameter Type

Read and Write

Factory Default

“Frequency”

Units

Display Drive

“Frequency” 0

Zero to programmed [Maximum Freq]

“Current” 1

Zero to 200%

“Torque” 2

Zero to 200%

“Power” 3

Zero to 200% kW

“Encoder” 4

Zero to [Pulse/Enc Hertz]

“Speed Adder” 5

Zero to [Speed Adder}

[Anlg Out Offset]

This parameter enables the voltage or current offset
for the analog output TB2 terminals 4 & 9. This
internal value offsets 0-20mA to 4-20mA and
0-10V to 2-10V.

Parameter Number

154

Parameter Type

Read and Write

Factory Default

“Disabled”

Units

Display Drive

“Disabled” 0

“Enabled” 1