Logic interface options appendix a – Rockwell Automation 1336 3-20HP FRN 1.01-3.01 User Manual

Page 103

Advertising
background image

Logic Interface Options

Appendix A

A-2

+5V DC

+5V DC

100

+5V DC

+5V DC

390

4.7k

390

+5V DC

+5V DC

100

4.7k

4.7k

390

100

+5V DC

390

+5V DC

+5V DC

100

4.7k

4.7k

390

100

+5V DC

390

+5V DC

100

4.7k

4.7k

390

100

+5V DC

390

+5V DC

100

4.7k

4.7k

390

100

EARTH

19

20

21

22

23

24

25

26

27

28

29

30

Aux

Enable

Rev

SW2

Speed
Select

I

GND

1336ĆMODĆL1

+5V DC TTL Logic Contact

Closure Interface Board (cont.)

3-Wire Control

TB3

19

20

21

22

23

24

25

26

27

28

29

30

2-Wire Control

TB3

Start/Stop

Contact

Start

Stop

Jog

+5V DC

SW1

GROUND

INTERFACE

COMMON

CHASSIS

GROUND

Maximum

Recommended

Signal

Wire Group ❶

Wire Size ❷

Torque ❸

Terminal 19, Interface Common

Start

5

14 AWG

7 In-Lbs

Terminal 20, Interface Common

Stop ❹

5

14 AWG

7 In-Lbs

Terminals 21, 25, 29

Interface Common

5

14 AWG

7 In-Lbs

Terminal 22, Interface Common

Jog

5

14 AWG

7 In-Lbs

Terminal 23, Interface Common

Reverse

5

14 AWG

7 In-Lbs

Terminal 24, Interface Common

SW1

5

14 AWG

7 In-Lbs

Terminal 26, Interface Common

SW2

5

14 AWG

7 In-Lbs

Terminal 27, Interface Common

Speed Select

5

14 AWG

7 In-Lbs

Terminal 28, Interface Common

Auxiliary ❹

5

14 AWG

7 In-Lbs

Terminal 30, Interface Common

Enable ❹

5

14 AWG

7 In-Lbs

❶ Wire group number chart, page 6-3.

❷ 2.5mm

2

.

❸ .79N-m.
❹ This signal must be present to permit the drive to operate from any control source.

Advertising