Terminal block tb1 - b100-b125 power wiring, Terminal block tb1 - c100-c125 power wiring – Rockwell Automation 1336 3-20HP FRN 1.01-3.01 User Manual

Page 60

Advertising
background image

Wiring

Chapter 6

6-13

TB1

L1

L2

L3

Fan 1

T1

415V AC

380V AC

460V AC

120V AC

1

2

TB4

B100ĆB125 Fan Transformer Wiring

Drives rated B100-B125 are shipped
from the factory with Fan Transformer
T1 connected for 460V operation. Fan
Transformer T1 has three tab
connections marked 460V, 380V and
415V. For 380 or 415V drive operation,
the Fan Transformer lead at
transformer T1 must be unplugged and
reconnected.

Terminal Block TB1 -

B100ĆB125 & C100ĆC125

Power Wiring (cont.)

C100ĆC125 Fan Transformer Wiring

For drives rated C100-C125, reconnection of Fan Transformer T1 is not
required for 500 or 575V AC operation.

Terminal Block TB1 -

B100ĆB125 Power Wiring

Power

Drive

Maximum

Rating

Output

Wire

Wire

Maximum

Code

Current

Group ❶

Size ❷

Torque ❸

B100

150 Amps

2

350 MCM

275 In-lbs

B125

180 Amps

2

350 MCM

275 In-lbs

❶ Wire group number chart, page 6-3.
❷ 185 mm

2

.

❸ 31.08 N-m.

Select from the following drive input fuses when using branch circuit protection.

Drive Rating B100

Fuse Size 200A

Fuse Type A4J, JJS or Equivalent

Drive Rating B125

Fuse Size 250A

Fuse Type A4J, JJS or Equivalent

Terminal Block TB1 -

C100ĆC125 Power Wiring

Power

Drive

Maximum

Rating

Output

Wire

Wire

Maximum

Code

Current

Group ❶

Size ❷

Torque ❸

C100

109 Amps

2

350 MCM

275 In-lbs

C125

138 Amps

2

350 MCM

275 In-lbs

❶ Wire group number chart, page 6-3.
❷ 185 mm

2

.

❸ 31.08 N-m.

Select from the following drive input fuses when using branch circuit protection.

Drive Rating C100

Fuse Size 125A

Fuse Type A4J, JJS or Equivalent

Drive Rating C125

Fuse Size 150A

Fuse Type A4J, JJS or Equivalent