Rockwell Automation 1336 3-20HP FRN 1.01-3.01 User Manual
Page 33
Specifications
Chapter 4
4-6
Output Power (cont.)
DC Boost:
11 selectable values from 0 to 48V DC peak.
– Adjustable from 0 to 115V DC through optional
programming.
Accel/Decel:
Two independently programmable accel times.
Two independently programmable decel times.
Each time may be programmed over a range from
0 to 600 seconds.
Intermittent
Programmable MOPC from 50 to 150% of rated output
Overload Capability: current for up to 1 minute maximum.
Inverse Time
Designed to meet NEC and UL equivalent requirements.
Overload Capability: Adjustable timing from 50 to 115% of rated drive current
(Main Control Board Firmware Version 1.10 limited to 100%).
Drive
180% of rated output current.
Overcurrent Trip:
Ground Fault:
Detects drive output ground fault path by sensing
unbalanced bus or input line currents.