Rockwell Automation 1336 3-20HP FRN 1.01-3.01 User Manual

Page 33

Advertising
background image

Specifications

Chapter 4

4-6

Output Power (cont.)

DC Boost:

11 selectable values from 0 to 48V DC peak.
– Adjustable from 0 to 115V DC through optional
programming.

Accel/Decel:

Two independently programmable accel times.
Two independently programmable decel times.
Each time may be programmed over a range from
0 to 600 seconds.

Intermittent

Programmable MOPC from 50 to 150% of rated output

Overload Capability: current for up to 1 minute maximum.

Inverse Time

Designed to meet NEC and UL equivalent requirements.

Overload Capability: Adjustable timing from 50 to 115% of rated drive current

(Main Control Board Firmware Version 1.10 limited to 100%).

Drive

180% of rated output current.

Overcurrent Trip:

Ground Fault:

Detects drive output ground fault path by sensing
unbalanced bus or input line currents.