Logic Interface Options

Appendix A

A-18

1336ĆMODĆL3 115V AC

Terminal 27 and Interface Common

Logic Interface Board

Speed Select

True = Select Parameter 6, Frequency Select 2

False = Select Parameter 5, Frequency Select 1

The drive speed reference can come from a variety of sources. Refer to
Chapter 8 — Speed Selection for details.

Terminal 28 and Interface Common

(This signal must be maintained as True to permit the drive

to operate from any control source.)

Auxiliary

Maintained True = Auxiliary Interlocks Are Closed

False = Auxiliary Interlocks Are Open

Auxiliary allows the drive to be interlocked using external interlocks. The
interlocks must be closed and this input True to permit the drive to operate.
When an interlock opens and the input is False for 90mS or longer, the
drive will initiate a programmed stop sequence and generate Fault F02.

Terminal 30 and Interface Common

(This signal must be maintained as True to permit the drive to operate from

any control source.)

Enable

Maintained True = Drive Enabled

False = Disable Drive

Enable must be a maintained True input to permit the drive to run and jog
the motor. If this input is False for 20mS or longer, drive operating
capabilities are not permitted and drive outputs are disabled forcing the
motor to coast-to-stop. Power however, is not be removed from the drive’s
control logic and drive programming can still be accessed.