Logic Interface Options

Appendix A

A-12

1336ĆMODĆL2 +24V DC

Terminal 30 and Interface Common

Logic Interface Board (cont.)

(This signal must be maintained as True to permit the drive to operate from any
control source.)

Enable

Maintained True = Drive Enabled

False = Disable Drive

Enable must be a maintained True input to permit the drive to run and jog
the motor. If this input is False for 20mS or longer, drive operating
capabilities are not permitted and drive outputs are disabled forcing the
motor to coast-to-stop. Power however, is not be removed from the drive’s
control logic and drive programming can still be accessed.