B003 b200 input power, C003 c200 input power – Rockwell Automation 1336 3-20HP FRN 1.01-3.01 User Manual
Page 30
Specifications
Chapter 4
4-3
B003ĆB200 Input Power
Voltage:
380-460V AC
±
10%.
Frequency:
48 to 62 Hz.
Phase:
3-phase.
AC Input Overvoltage Trip:
570V AC.
AC Input Undervoltage Trip: 275V AC.
Bus Overvoltage Trip:
810V DC for drive ratings B003-B200.
Bus Undervoltage Trip:
388V DC for Base Driver/Power Supply
Board.
Firmware Versions 1.11-3.01.
456V DC for Base Driver/Power Supply
Board.
Firmware Version 1.01.
Line Transient Protection:
Line transients up to 5,000 volts peak, 320
Joules.
Logic Power Ride-Thru:
2 seconds or Longer.
–– subject to the integrity of user supplied
external circuits.
Control Logic Noise:
Showering arc transients from 350 to 2,000
Immunity
volts peak.
C003ĆC200 Input Power
Voltage:
500-575V AC
±
10%.
Frequency:
48 to 62 Hz.
Phase:
3-phase.
AC Input Overvoltage Trip:
690V AC.
AC Input Undervoltage Trip: 343V AC.
Bus Overvoltage Trip:
975V DC.
Bus Undervoltage Trip:
485V DC.
Line Transient Protection:
Line transients up to 5,000 volts peak, 320
Joules.
Logic Power Ride-Thru:
2 seconds or Longer.
–– subject to the integrity of user supplied
external circuits.
Control Logic Noise:
Showering arc transients from 350 to 2,000
Immunity
volts peak.