B003 b200 input power, C003 c200 input power – Rockwell Automation 1336 3-20HP FRN 1.01-3.01 User Manual

Page 30

Advertising
background image

Specifications

Chapter 4

4-3

B003ĆB200 Input Power

Voltage:

380-460V AC

±

10%.

Frequency:

48 to 62 Hz.

Phase:

3-phase.

AC Input Overvoltage Trip:

570V AC.

AC Input Undervoltage Trip: 275V AC.

Bus Overvoltage Trip:

810V DC for drive ratings B003-B200.

Bus Undervoltage Trip:

388V DC for Base Driver/Power Supply
Board.
Firmware Versions 1.11-3.01.

456V DC for Base Driver/Power Supply
Board.
Firmware Version 1.01.

Line Transient Protection:

Line transients up to 5,000 volts peak, 320
Joules.

Logic Power Ride-Thru:

2 seconds or Longer.
–– subject to the integrity of user supplied
external circuits.

Control Logic Noise:

Showering arc transients from 350 to 2,000

Immunity

volts peak.

C003ĆC200 Input Power

Voltage:

500-575V AC

±

10%.

Frequency:

48 to 62 Hz.

Phase:

3-phase.

AC Input Overvoltage Trip:

690V AC.

AC Input Undervoltage Trip: 343V AC.

Bus Overvoltage Trip:

975V DC.

Bus Undervoltage Trip:

485V DC.

Line Transient Protection:

Line transients up to 5,000 volts peak, 320
Joules.

Logic Power Ride-Thru:

2 seconds or Longer.
–– subject to the integrity of user supplied
external circuits.

Control Logic Noise:

Showering arc transients from 350 to 2,000

Immunity

volts peak.