Wiring

Chapter 6

6-11

TB1

L1

L2

L3

Fan 1

T1

415V AC

380V AC

460V AC

120V AC

1

2

TB4

B075 Fan Transformer Wiring

Drives rated B075 are shipped from
the factory with Fan Transformer T1
connected for 460V operation. Fan
Transformer T1 has three tab
connections marked 460V, 380V and
415V. For 380 or 415V drive
operation, the Fan Transformer lead
at transformer T1 must be
unplugged and reconnected.

Terminal Block TB1 -

B075 & C075 Power Wiring

(cont.)

C075 Fan Transformer Wiring

For drives rated C075, reconnection of Fan Transformer T1 is not required
for 500 or 575V AC operation.

Terminal Block TB1 -

B075 Power Wiring

Power

Drive

Maximum

Rating

Output

Wire

Wire

Maximum

Code

Current

Group ❶

Size ❷

Torque ❸

B075

120 Amps

2

2/0 AWG

120 In-lbs

❶ Wire group number chart, page 6-3.
❷ 70 mm

2

.

❸ 13.56 N-m.

Select from the following drive input fuses when using branch circuit protection.

Drive Rating B075

Fuse Size 150A

Fuse Type A4J, JJS or Equivalent

Terminal Block TB1 -

C075 Power Wiring

Power

Drive

Maximum

Rating

Output

Wire

Wire

Maximum

Code

Current

Group ❶

Size ❷

Torque ❸

C075

85 Amps

2

2/0 AWG

120 In-lbs

❶ Wire group number chart, page 6-3.
❷ 70 mm

2

.

❸ 13.56 N-m.

Select from the following drive input fuses when using branch circuit protection.

Drive Rating C075

Fuse Size 90A

Fuse Type A4J, JJS or Equivalent