Wiring

Chapter 6

6-22

Terminal Block TB2 -

Terminals 10 and 11

Control and Signal Wiring (cont.)

At Speed

These terminals allow an internal drive supplied at speed contact to be used
in external circuits. Parameter 77 allows the at speed contact to be
programmed to change state within

±

0.5% of maximum speed for one of

two conditions –– When the drive reaches command speed or when the
drive reaches a programmed set point reference frequency. The contact is
isolated from logic and other drive circuitry.

Resistive rating: 120V AC or 30V DC, 5.0 amps

Inductive rating: 120V AC or 30V DC, 2.0 amps

Terminals 11 and 12

Run

These terminals allow an internal drive supplied run contact to be used in
external circuits. The N.O. contact closes when the drive is running and
opens when the drive is stopped and not generating any output to the
connected load. The contact is isolated from logic and other drive circuitry.

Resistive rating: 120V AC or 30V DC, 5.0 amps

Inductive rating: 120 V AC or 30V DC, 2.0 amps

Terminals 13, 14, 15

Fault

These terminals allow internal drive supplied fault contacts to be used in
external circuits. The contacts are shown in the de-energized (faulted) state.
When the drive is powered up and no fault is present, the contacts will
change state, 13 to 14 will open, 14 to 15 will close.

Both the N.C. and N.O. contacts will change state
(13 to 14 will close, 14 to 15 will open) when the drive has detected a Fault
or power is removed from the drive.

Resistive rating: 120V AC or 30V DC, 5.0 amps

Inductive rating: 120 V AC or 30V DC, 2.0 amps