Logic interface options appendix a, A-15 – Rockwell Automation 1336 3-20HP FRN 1.01-3.01 User Manual

Page 116

Advertising
background image

Logic Interface Options

Appendix A

A-15

5.6k

5.6k

5.6k

5.6k

5.6k

5.6k

5.6k

5.6k

5.6k

5.6k

5.6k

5.6k

5.6k

5.6k

5.6k

5.6k

5.6k

5.6k

19

20

21

22

23

24

25

26

27

28

29

30

I

K9

K8

K7

K6

K5

K4

K3

K2

K1

Aux

Enable

Start

Stop

Jog

Rev

SW2

Speed
Select

User 115V AC Supply

EARTH

GROUND

3-Wire Control

2-Wire Control

TB3

TB3

19

20

21

22

23

24

25

26

27

28

29

30

User 115V AC Supply

Start/Stop

Contact

INTERFACE

COMMON

SW1

EARTH

GROUND

1336ĆMODĆL3 115V AC

Logic Interface Board (cont.)

Maximum

Recommended

Signal

Wire Group ❶

Wire Size ❷

Torque ❸

Terminal 19, Interface Common

Start

3

14 AWG

7 In-Lbs

Terminal 20, Interface Common

Stop ❹

3

14 AWG

7 In-Lbs

Terminals 21, 25, 29

Interface Common

3

14 AWG

7 In-Lbs

Terminal 22, Interface Common

Jog

3

14 AWG

7 In-Lbs

Terminal 23, Interface Common

Reverse

3

14 AWG

7 In-Lbs

Terminal 24, Interface Common

SW1

3

14 AWG

7 In-Lbs

Terminal 26, Interface Common

SW2

3

14 AWG

7 In-Lbs

Terminal 27, Interface Common

Speed Select

3

14 AWG

7 In-Lbs

Terminal 28, Interface Common

Auxiliary ❹

3

14 AWG

7 In-Lbs

Terminal 30, Interface Common

Enable ❹

3

14 AWG

7 In-Lbs

❶ Wire group number chart, page 6-3.

❷ 2.5mm

2

.

❸ .79N-m.
❹ This signal must be present to permit the drive to operate from any control source.