Chapter 9

9-2

Initial Operation

Step 1

- Motor Disconnected

Verify that AC line power at the disconnect device is within the rated value
of the drive. Drive nameplate and alternate voltage ratings are listed in
Chapter 2 — Drive and Option Identification.

Step 2

Remove and lock out all incoming power to the drive. Remove the drive
cover and disconnect motor leads from drive terminals M1, M2 and M3.

Step 3

If one of the following optional interface boards is installed:

1336-MOD-L1
1336-MOD-L2
1336-MOD-L3

Verify that interface input connections to the board match the voltage
rating of the board.

Verify that enable and auxiliary interlock inputs are provided.

Step 4

If option L1, L2 or L3 is not installed, verify that the three spare jumpers
provided with the drive are installed correctly at connectors J8 and J9.

Control Board connector J8 –– Pins 11 and 12 jumpered

Control Board connector J9 –– Pins 7 and 8 jumpered

Pins 9 and 10 jumpered

Step 5

Confirm that all other optional inputs are connected to their correct
terminals and are secure.

Step 6

Replace the drive cover and tighten all thumbscrews.