Rockwell Automation 1336 3-20HP FRN 1.01-3.01 User Manual

Page 85

Advertising
background image

Startup

Chapter 9

9-7

Initial Operation

Step 11

- Motor Disconnected (cont.)

With the Control Panel speed pot active (Pr display = - 0), turn the speed
pot fully counterclockwise.

Stop

Reset the drive by pressing the Stop pushbutton.

Start

Press the Start pushbutton and start the drive.

The drive will ramp to the minimum speed set by Parameter 16.

Important: If a dwell frequency is programmed, the drive will first jump
to the dwell frequency for the dwell time, then ramp to the minimum
frequency value set by Parameter 16.

Step 12

While the drive is running, turn the local speed pot fully clockwise. The
drive will ramp to the maximum output frequency value set by Parameter
19.

Step 13

Press the direction pushbutton.

If reversing is active (Parameter 22 = 1), the drive will ramp to zero speed,
then ramp to maximum speed as indicated on the display panel. The LEDs
on the Control Panel will switch to the selected direction of rotation.

If reversing is not active (Parameter 22 = 0), pressing the direction
pushbutton will not change drive direction, and the same directional LED
on the Control Panel will remain lit.