Startup

Chapter 9

9-6

Initial Operation

Step 9c

- Motor Disconnected (cont.)

The default selection or the speed source selected with the speed select
open is the source programmed in Parameter 5. Parameter 5 may be one of
the following values:

Freq

P

R

Pr = - 0 if Parameter 5 = 0, Control Panel speed potentiometer

Pr = - 1 if Parameter 5 = 1, 0-10V DC input.

Pr = - 2 if Parameter 5 = 2, 4-20mA input.

Pr = - 3 if Parameter 5 = 3, pulse train input.

Pr = - 4 if Parameter 5 = 4, serial input.

Pr = - 5 if Parameter 5 = 5, remote speed potentiometer input.

Check Parameter 84 – Analog Inverse.

If set to 1 (On), the 0-10V DC or 4-20mA input signals at Terminal Block
TB2 in the drive will produce an inverse speed signal.

A 0V DC or 4mA signal will produce maximum drive output frequency as
set by Parameter 19. A 10V DC or 20mA signal will produce minimum
drive output frequency as set by Parameter 16.

Step 10

For convenience, the control elements on the Control Panel should be
active.

Verify or change the following parameters:

Set Parameter 5, Frequency Select = 0 (Control Panel speed pot active).

Set Parameter 21, Local Run = 1 (allow Control Panel run control).

For local reversing, set Parameter 22, Local Reverse = 1 (allow Control
Panel reverse control).

If jog is desired, set Parameter 23, Local Jog = 1 (allow Control Panel jog
control).

Return to the operating mode.