Startup

Chapter 9

9-11

Initial Operation

Step 23

- Motor Connected (cont.)

Turn the Control Panel speed pot fully counterclockwise.

Start

Start the drive.

Slowly increase motor speed and check for proper motor operation
throughout the speed range of the drive.

Step 24

With the drive operating at 1/4 speed or greater:

Stop

Stop the drive and verify that the stopping mode selected by Parameter 10
occurs.

Step 25

Stop

Stop the drive.

P

R

Press Pr to enter the programming mode and reset the parameters in Step
21 and any other parameters that were changed during the setup procedure.

Review each parameter description in the Programming Manual.
Determine the value required for the application and set the parameter.
Make a record of any “estimated” values.

Press ▲ and ▼ simultaneously to return to the operating mode.