Operation

Chapter 7

7-2

If this sequence is not followed, the drive will fault and display F11.
When Parameter 14 is set to 0, the stop command must be repeated twice,
once to clear the fault, then again to reset drive logic once the fault has
been cleared.

A stop input is any valid stop signal that the drive receives. Valid stop
inputs are:

The Stop pushbutton on a Control Panel –– As shown on the following
page.

The stop input wired to TB3 at Terminal 20 –– As explained in
Appendix A, Logic Interface Options.

When serial communications is used, writing to Parameter 51 to clear
the fault, then setting the stop bit of the serial input control word in
Parameter 57 –– As explained in the 1336 Programming Manual.

Local or Remote Control Panel

Start

Jog

Stop

!

ATTENTION: Unexpected machine motion can cause injury or
death. Do not use a Local or Remote Control Panel with option L1,
L2, or L3 in any 2-wire start/stop control application.

A maintained start command or 2-wire control between terminals
19 and 20 of TB3 on option L1, L2 or L3 will affect Control Panel
stop pushbutton operation. The drive will automatically restart after
the Control Panel stop pushbutton is depressed and released.