Logic interface options appendix a – Rockwell Automation 1336 3-20HP FRN 1.01-3.01 User Manual
Page 109
Logic Interface Options
Appendix A
A-8
I
K9
K8
K7
K6
K5
K4
K3
K2
K1
3-Wire Control
2-Wire Control
TB3
19
20
21
22
23
24
25
26
27
28
29
30
+
–
User +24V DC Supply
TB3
19
20
21
22
23
24
25
26
27
28
29
30
+
–
User +24V DC Supply
Aux
Enable
Rev
SW2
Speed
Select
Start/Stop
Contact
Start
Stop
Jog
INTERFACE
COMMON
SW1
1336ĆMODĆL2 +24V DC
Logic Interface Board (cont.)
Maximum
Recommended
Signal
Wire Group ❶
Wire Size ❷
Torque ❸
Terminal 19, Interface Common
Start
4
14 AWG
7 In-Lbs
Terminal 20, Interface Common
Stop ❹
4
14 AWG
7 In-Lbs
Terminals 21, 25, 29
Interface Common
4
14 AWG
7 In-Lbs
Terminal 22, Interface Common
Jog
4
14 AWG
7 In-Lbs
Terminal 23, Interface Common
Reverse
4
14 AWG
7 In-Lbs
Terminal 24, Interface Common
SW1
4
14 AWG
7 In-Lbs
Terminal 26, Interface Common
SW2
4
14 AWG
7 In-Lbs
Terminal 27, Interface Common
Speed Select
4
14 AWG
7 In-Lbs
Terminal 28, Interface Common
Auxiliary ❹
4
14 AWG
7 In-Lbs
Terminal 30, Interface Common
Enable ❹
4
14 AWG
7 In-Lbs
❶ Wire group number chart, page 6-3.
❷ 2.5mm
2
.
❸ .79N-m.
❹ This signal must be present to permit the drive to operate from any control source.