Chapter 9

9-13

Initial Operation

Step 27

- Motor Connected (cont.)

(cont.)

Apply power. Prepare to operate the drive and motor under actual control
and load conditions. It is desirable to begin at low torque and speed.

Start

Start the motor and run the machine or process to determine if parameter
settings are acceptable for the application.

Stop

Stop the motor.

P

R

Press Pr to enter the programming mode if changes in parameter values are
necessary. Refer to the Programming Manual each time a change is made
to a parameter. Record each setting and the corresponding drive, motor,
and machine behavior (or process deviation) for future reference.

Simultaneously press ▲ and ▼ to return to the operating mode.

After achieving satisfactory operation, record all final parameter values in
the Programming Manual.

Step 28

Stop

Stop the drive. Disconnect and lock-out all power.

SW1

C1

C2

If the chassis mounted Local Programming and Display Panel is installed,
the programming ability may be disabled by setting SW1 to C2. This
concludes the initial startup procedure.