Logic Interface Options

Appendix A

A-17

1336ĆMODĆL3 115V AC

Terminals 21, 25, 29

Logic Interface Board

Interface Common

Terminals 21, 25 and 29 are used to terminate both minus or interface
common signals to TB3. Terminals 21, 25 and 29 are also used to terminate
any shields for cables connected to TB3. For the 1336-MOD-L3 115V AC
Logic Interface Board, Terminals 21, 25 and 29 are isolated from drive
signal common, chassis ground, and earth ground.

Terminal 22 and Interface Common

Jog

True = Jog

False = Interrupt Jog and Allow Other Functions

This input will jog the drive if it is not running and interlocks permit. As
long as interlocks permit and the jog command remains True, the drive will
continue to run at the programmed jog frequency.

Terminal 23 and Interface Common

Reverse

Maintained True = Reverse

Maintained False = Forward

Parameter 22 enables the direction of drive rotation to be controlled by an
input at Terminal 23. A maintained False will select the forward direction,
a maintained true the reverse direction.

Terminal 24 and Interface Common

SW1

True = SW1 Function Selected

False = SW1 Function Not Selected

Parameters 26-31 and 72-76 define the SW1 function.

Terminal 26 and Interface Common

SW2

True = SW2 Function Selected

False = SW2 Function Not Selected

Parameters 26-31 and 72-76 define the SW2 function.