Wiring

Chapter 6

6-9

Terminal Block TB1 -

B040ĆB050 Fan Transformer Wiring

B040ĆB050 & C040ĆC050

Drives rated B040-B050 are shipped from the factory with Fan

Power Wiring (cont.)

Transformer T1 connected for 460V operation. Fan Transformer T1 has
three leads marked 460V, 380V and 415V, each terminated by a keyed
connector. For 380 or 415V drive operation, the Fan Transformer lead at
L2 must be unplugged and reconnected as shown on the previous page.

C040ĆC050 Fan Transformer Wiring

For drives rated C040-C050, reconnection of fan transformer T1 is not
required for 500 or 600V AC operation.

Terminal Block TB1 -

B040ĆB050 Power Wiring

Power

Drive

Maximum

Rating

Output

Wire

Wire

Maximum

Code

Current

Group ❶

Size ❷

Torque ❸

B040

60 Amps

2

2/0 AWG

120 In-lbs

B050

75 Amps

2

2/0 AWG

120 In-lbs

❶ Wire group number chart, page 6-3.
❷ 70 mm

2

.

❸ 13.56 N-m.

Select from the following drive input fuses when using branch circuit protection.

Drive Rating B040

Fuse Size 80A

Fuse Type A4J, JJS or Equivalent

Drive Rating B050

Fuse Size 100A

Fuse Type A4J, JJS or Equivalent

Terminal Block TB1 -

C040ĆC050 Power Wiring

Power

Drive

Maximum

Rating

Output

Wire

Wire

Maximum

Code

Current

Group ❶

Size ❷

Torque ❸

C040

45 Amps

2

2/0 AWG

120 In-lbs

C050

57 Amps

2

2/0 AWG

120 In-lbs

❶ Wire group number chart, page 6-3.
❷ 70 mm

2

.

❸ 13.56 N-m.

Select from the following drive input fuses when using branch circuit protection.

Drive Rating C040

Fuse Size 45A

Fuse Type A4J, JJS or Equivalent

Drive Rating C050

Fuse Size 60A

Fuse Type A4J, JJS or Equivalent