Logic Interface Options

Appendix A

A-11

1336ĆMODĆL2 +24V DC

Terminal 24 and Interface Common

Logic Interface Board (cont.)

SW1

True = SW1 Function Selected

False = SW1 function not selected

Parameters 26-31 and 72-76 define the SW1 function.

Terminal 26 and Interface Common

SW2

True = SW2 Function Selected

False = SW2 Function Not Selected

Parameters 26-31 and 72-76 define the SW2 function.

Terminal 27 and Interface Common

Speed Select

True = Select Parameter 6, Frequency Select 2

False = Select Parameter 5, Frequency Select 1

The drive speed reference can come from a variety of sources. Refer to
Chapter 8 — Speed Selection for details.

Terminal 28 and Interface Common

(This signal must be maintained as True to permit the drive

to operate from any control source.)

Auxiliary

Maintained True = Auxiliary Interlocks Are Closed

False = Auxiliary Interlocks Are Open

Auxiliary allows the drive to be interlocked using external interlocks. The
interlocks must be closed and this input True to permit the drive to operate.
When an interlock opens and the input is False for 20mS or longer, the
drive will initiate a programmed stop sequence and generate Fault F02.