Chapter 10

10-5

Ground Fault

Freq

P

R

A current path to earth ground has been detected at one or more of the
drive output terminals. Check the motor and external wiring to the drive
output terminals for a grounded condition.

U VW Output Short

Freq

P

R

A short circuit has been detected between two or more of the drive output
terminals. Check the motor and external wiring to the drive output
terminals for a shorted condition.

V UW Output Short

Freq

P

R

A short circuit has been detected between two or more of the drive output
terminals. Check the motor and external wiring to the drive output
terminals for a shorted condition.

W UV Output Short

Freq

P

R

A short circuit has been detected between two or more of the drive output
terminals. Check the motor and external wiring to the drive output
terminals for a shorted condition.

Negative Phase Transistor Short

Freq

P

R

A shorted drive transistor has been detected. Check drive output transistors,
both upper and lower portions of each transistor, for a shorted condition.