Dc, - dc, M1, m2, m3, L1, l2, l3 – Rockwell Automation 1336 3-20HP FRN 1.01-3.01 User Manual

Page 55: Connect the motor leads to these terminals

Advertising
background image

Wiring

Chapter 6

6-8

Terminal Block TB1 -

B040ĆB050 & C040ĆC050 Power Wiring

GND

+DC

–DC

M1

M2

M3

L1

L2

L3

GND

A

Transform

er

T1

B

C

A

B

C

Earth

Groun

d

1336

Dynamic

Brake

Motor

AC Incoming Line

Earth

Groun

d

USE 75

°

C COPPER WIRE ONLY WIRE RANGE 2/0 – 6 AWG

TIGHTENING TORQUE 120 INCH POUNDS

User supplied drive input fuses.

Motor disconnecting means including branch circuit,

short circuit, and ground fault protection.

460V

380V

415V

GND

Chassis ground is used to connect the drive chassis to a common ground.
The motor frame must also be connected to the same common ground.
Either earth ground or the ground of the building system must be used.
Refer to the motor manufacturer’s guidelines for additional information.

+ DC, - DC

DC bus terminals are reserved for the 1336 dynamic brake option. Refer to
the 1336 dynamic brake option instructions for installation and connection
details.

M1, M2, M3

Connect the motor leads to these terminals.

L1, L2, L3

Input AC line Terminals L1, L2, L3 (

A,

B,

C) are not phase

sensitive.

For drives rated B040-B050, nominal input voltage is 380/415/460V AC

±

10%, 3

, 50/60Hz.

For drives rated C040-C050, nominal input voltage is 500 or 575V AC

±

10%, 3

, 50/60Hz.

Branch disconnect and short circuit protection is not part of the standard
1336 and must be supplied by the user. Drive input fuses are required to
provide component protection against malfunction of electronic circuits.

Advertising