4 - specifications, Operating environment, Storage environment – Rockwell Automation 1336 3-20HP FRN 1.01-3.01 User Manual

Page 28: Enclosure, Specifications

Advertising
background image

4

Chapter

4-1

Specifications

Operating Environment

Temperature:

Open rating (heat sink), 0 to + 40

°

C.

Open rating (chassis components), 0 to +50

°

C.

Enclosed rating (heat sink), 0 to + 40

°

C.

Enclosed rating (chassis components), 0 to +50

°

C.

Relative Humidity: 5 to 95% non-condensing –– all ratings.

Altitude:

3,300 feet (1,000 meters) maximum without derating.

Vibration:

0.006 inches (0.152 mm) displacement, 1G peak.

Shock:

15G peak for 11ms duration (

±

1.0mS).

Storage Environment

Temperature:

– 40 to +85

°

C –– all ratings.

Relative Humidity: 5 to 95% non-condensing –– all ratings.

Enclosure

Indicated by Catalog Number.

Open (IP00) –– all ratings.

NEMA Type 1 (IP20) –– all ratings.

NEMA Type 4 (IP56), B003-B030 & C003-C030.

NEMA Type 12 (IP54), B003-B200 & C003-C200.