Speed Selection

Chapter 8

8-2

Priority 3 - Speed Select Input Is

The speed source programmed by Parameter 6 will be selected when the

True

speed select input at Terminal 27 is true. Parameter 6 may be programmed

- Parameter 6

for one of the following six sources:

Freq

P

R

Pr = - 0 if Parameter 6 = 0, Control Panel speed potentiometer

Pr = - 1 if Parameter 6 = 1, 0-10V DC input.

Pr = - 2 if Parameter 6 = 2, 4-20mA input.

Pr = - 3 if Parameter 6 = 3, pulse train input.

Pr = - 4 if Parameter 6 = 4, serial input.

Pr = - 5 if Parameter 6 = 5, remote speed potentiometer input.

Priority 4 - Speed Select Input Is

The speed source programmed by Parameter 5 will be selected when the

False

speed select input at Terminal 27 is false. The speed source programmed

- Parameter 5

by Parameter 5 will be the default speed source, the lowest speed source
priority. Parameter 5 may be programmed for one of the following six
sources:

Freq

P

R

Pr = - 0 if Parameter 5 = 0, Control Panel speed potentiometer.

Pr = - 1 if Parameter 5 = 1, 0-10V DC input.

Pr = - 2 if Parameter 5 = 2, 4-20mA input.

Pr = - 3 if Parameter 5 = 3, pulse train input.

Pr = - 4 if Parameter 5 = 4, serial input.

Pr = - 5 if Parameter 5 = 5, remote speed potentiometer input.