Configuration

28

Level 3 Submenus

EDP Port

BAUD

9600
19200
300
600
1200
2400
4800

Baud rate. Selects the transmission speed for the EDP port.

BITS

8NONE
7EVEN
7ODD

Selects number of data bits and parity of data transmitted from the EDP port.

TERMIN

CR/LF
CR

Termination character. Selects termination character for data sent from the EDP port.

ECHO

ON
OFF

Allows the echo to be turned on or off.

EOLDLY

0000000
0–255

End-of-line delay. Sets the delay period, in 0.1-second intervals, from when a formatted line is
terminated to the beginning of the next formatted serial output. Value specified must be in the
range 0-255, in tenths of a second (10 = 1 second).

HANDSHK

OFF
ON

Specifies whether XON/XOFF flow control characters are used.

ADDRESS

0000000
0–255

Specifies the decimal indicator address for RS-485 connections. RS-232 communications is
disabled if an address other than zero is specified for this parameter. RS-485 addresses must be
in the range 0–255.

STREAM

OFF
LFT
IND

Specifies whether data is streamed from the EDP port.

OFF: Data is not streamed from the EDP port
LFT (Legal-for-Trade): Data is streamed at the display update rate
IND (Industrial): Data is streamed at the A/D update rate

FORMAT

DEFLT 7
DEFLT 8
CUSTOM
BUS FMT

Specifies whether the serial port sends data using the default stream format (using either 7 or 8
weight digits), a custom stream format (configured in STRMFMT; see Figure 3-10 on page 34), or
is streamed to a network bus (Profibus, Remote I/O, DeviceNet). For more specific information
on CUSTOM stream format, see Table 12-5 on page 77. BUS FMT is only used with serial bus
options.

Level 3 Submenus

Printer Port

BAUD

9600
19200
300
600
1200
2400
4800

Baud rate. Selects the transmission speed for the printer port.

BITS

8NONE
7EVEN
7ODD

Selects number of data bits and parity of data transmitted from the printer port.

TERMIN

CR/LF
CR

Termination character. Selects termination character for data sent from the printer port.

ECHO

ON
OFF

Allows the Print Echo to be turned on or off.

EOLDLY

0000000
0-255

End-of-line delay. Sets the delay period, in 0.1-second intervals, from when a formatted line is
terminated to the beginning of the next formatted serial output. Value specified must be in the
range 0-255, in tenths of a second (10 = 1 second).

SERIAL Menu

Parameter

Choices

Description

Table 3-5. Serial Menu Parameters (Continued)