ALARM

OFF
ON

GROSSSP, NETSP, RELSP, DELAY, and WAITSS setpoint types: Specify ON to
display the word ALARM on the primary display while the setpoint is active (batch
setpoints) or while the setpoint is not tripped (continuous setpoints).

START

1–8

TIMER and CONCUR setpoint types: Specifies the starting setpoint number. Do not
specify the number of the TIMER or CONCUR setpoint itself. The TIMER or
CONCUR setpoint begins when the starting setpoint begins.

END

1–8

TIMER and CONCUR setpoint types: Specifies the ending setpoint number. Do not
specify the number of the TIMER or CONCUR setpoint itself. The TIMER or
CONCUR setpoint stops when the ending setpoint begins.

ACCESS

ON
HIDE
OFF

All setpoint types: Specifies whether or not the setpoint can be accessed in weigh
mode via the front panel entry mode.

ON: Value can be displayed and changed
HIDE: Value cannot be displayed or changed
OFF: Value can be displayed but not changed

Setpoints with ACCESS=ON can be turned on or off when a batch is not running:

To turn the setpoint on/off, enter front panel setup mode (push and hold UNITS

key). Select setpoint by pressing UNITS or PRINT (

or

). Turn setpoint on/off by

pressing GROSS/NET

( ).

NAME

NONE, 1–8

All setpoint types: Specify the number of an assigned prompt. Up to 8 prompt names
can be specified on the PROMPTS submenu of the PROGRM menu.

DIGOUT

NONE, 1–4

All setpoint types: Specifies a digital output associated with the setpoint. For
continuous setpoints, the digital output becomes active (low) when the condition is
met; for batch setpoints, the digital output is active until the setpoint condition is met.

SETPTS Menu

Parameter

Choices

Description

Table 11-2. Setpoint Menu Parameters (Continued)