Setpoints

72

11.3

Batching Switch

The batching switch option, PN 19369, comes as a

complete unit in an FRP enclosure, with legend plate,

locking stop switch (mushroom button), and a

run/start/abort 3-way switch.

ABORT ST

ART

RUN

EMERGENCY

ST OP

IN-ST OP OUT

-RUN

Figure 11-6. Batching Switch

Both switches are wired into the indicator's digital I/O

terminal strip as shown in Figure 11-7. Each switch

uses a separate digital input.
Once cables and switches have been connected to the

indicator, use the setup switch to place the indicator in

setup mode. Use the DIGIN menu (see Section 3.2.8 on

page 38) to configure digital input functions. The

default values for DIGIN1 and DIGIN2 are BATSTRT

and BATRUN, respectively.
When configuration is complete, exit setup mode.

Initialize the batch by turning the 3-way switch to

ABORT

, then unlock the STOP button (the STOP button

must be in the OUT position to allow the batch process

to run). The batching switch is now ready to use.

3&%

8)*5&

#-"$,

3&%

#-"$,

450145"35.64)300.48*5$)

"#03536/45"3548*5$)

"
#
0
3
5

4
5
"
3
5

















/0

/$

/$

/0

/0

+

PO$16#PBSE

 7

 (/%

 %0

%0



%0



%0



%*



%*



%*



(/%



%*(*5

"-*/165065165

WARNING

If no digital input is assigned to BATRUN,
batching proceeds as if BATRUN were
always on: If DIGIN2 is not assigned to
BATRUN, the batch will start when the
3-way switch is turned to START, but the
STOP mushroom button will not function.

Figure 11-7. Batching Switch Wiring Diagram

To begin a batch process, turn the 3-way switch to

START

momentarily. If the STOP button is pushed

during the batch process, the process halts and the

button locks in the IN position.
The

START

switch is ignored while the STOP button is

locked in the IN position. The STOP button must be

turned counterclockwise to unlock it, then released into

the OUT position to enable the 3-way switch.
To restart an interrupted batch from the step where it

left off, do the following:

1. Unlock STOP button (OUT position)
2. Turn 3-way switch to

START

To restart an interrupted batch from the first batch step,

do the following:

1. Turn 3-way switch to

ABORT

2. Unlock STOP button (OUT position)
3. Turn 3-way switch to

START

Note

Use this procedure (or the BATRESET EDP command) to initialize the new batch routine following any change
to the setpoint configuration.