Series/parallel, Shorts, Opens – Cub Cadet SLTX1000 Series User Manual

Page 183: Increased resistance, Series/parallel shorts opens increased resistance

Advertising
background image

Electrical System

177

Series/parallel

Series/parallel circuits have some sections wired in
series and some in parallel. See Figure 7.50.

What can go wrong?

There are three types of failures that can occur in an electrical circuit:

1.

Shorts

2.

Opens

3.

Increased resistance

Shorts

A short is when electricity takes a path that it was not designed to take bypassing a component in the circuit.

A common example of a short is a wire with insulation that chafed through, exposing the copper conductor. The

bare copper will short the circuit when it touches a ground source.

Opens

An open is when current can not complete its path back to the power source. A common example of this is a

burned-out bulb in a series circuit.

Increased resistance

Increased resistance is, as the name implies, an increase in resistance.

This can be caused by loose or corroded connections, or connections that are insulated by grease, paint, or coat-

ings. Fasteners finished in oil and phosphate or black oxide are bad conductors. The use of zinc coated fasteners is
recommended.

Resistance can be a problem on the ground side as well as the hot side of a system. Remember that electricity

must complete a loop (circuit) back to the battery post. Any resistance in that loop will interfere with the flow.

Arguably, the most common electrical failure and the hardest to find, is increased resistance. It can have more

subtle symptoms than outright open circuits. Many times affected circuits will still partially function. It is not an “open”
because there is some current that can get through, but the increase in resistance is enough to affect the circuit.

Figure 7.50

Battery

Lamp Switch

Lamp

Lamp

Lamp

Advertising
This manual is related to the following products: