Typical applications, Features and capabilities, Hardy process toolbox – Hardy HI 6300 Series User Manual

Page 10: C2® and ecal™ calibration, Waversaver

Advertising
background image

2 Chapter

1

The HI 6300 series can be used with or without a display. The display is a bright 4.3”
high-contrast LCD capable of high-resolution graphics and discrete messaging. The
unit can be panel mounted, DIN mounted, and remote display mounted. The thin
enclosure and ultra-low power consumption allows for high density control cabinet
design.

Typical Applications

The HI 6300 series serves a variety of industrial weighing applications found in batching,
blending, filling, dispensing, inventory management, level by weight and check by weight
verification.

Features and Capabilities

Hardy Process Toolbox

The Hardy Process Toolbox is a set of productivity tools that support process weighing
functions. Each tool in the Hardy Process Toobox saves time, increases accuracy, improves
efficiency or reduces risk in process weighing applications. The HI 6300 includes the
following Toolbox functions.

C2

®

and eCal™ Calibration

Traditional calibration uses certified test weights. C2

®

(or eCAL

™ as it is called in China)

Electronic Calibration allows a scale to be calibrated without the need for test weights. A
C2 or eCAL weighing system consists of up to four load cell sensors per channel, a junction
box, interconnect cable, and an instrument with C2 capabilities (e.g., the HI 6300 series
instrument). Each Hardy Process Solutions C2-certified load sensor outputs digital
information used for calculating the calibration. When the HI 6300 series instrument reads
the signals from the load sensors, it calibrates the scale based on the load sensor’s output
plus a user-supplied reference point value (from 0 to any known weight on the scale).

WAVERSAVER

®

When measuring small weight changes, the effects of mechanical vibration and noise from
feeders and other plant environmental conditions can introduce substantial interference.
WAVERSAVER factors out vibration, noise, and other interference-related signals from the
load cell so the rate controller can better decipher the actual weight data.

While WAVERSAVER can factor out noise with frequencies as low as 1.00 Hz, three cut-
off frequencies can be selected, with higher frequencies providing a faster response time.
The default factory setting is 1.00 Hz vibration frequency immunity.

Advertising