Hardy HI 6300 Series User Manual

Page 43

Advertising
background image

Network Configuration 35

Calibration_Fail 1

Calibration_Fail_Motion 3

Calibration_Fail_Adc_Error 4

0x65 (101decimal): CAL HIGH CMD. Write a 0x65 hex to the command register to

perform the high step of a traditional calibration.

Calibration_Fail 1

Calibration_Fail_Motion 3

Calibration_Fail_Adc_Error 4

HardcalFailCounts 8: not enough counts between hard cal hi and hard cal lo

0x66 (102 decimal): C2 CAL CMD. Write a 0x66 hex to the command register to

perform a C2 calibration.

Calibration_Fail 1

Calibration_Fail_Motion 3

Calibration_Fail_Adc_Error 4

Calibration_Fail_Noc2 5

Calibration_Fail_C2capeq 6

Calibration_Fail_C2clones 7

0x1000 (4096 decimal): WRITE INTEGER CMD. Set the value of an integer

parameter. Write 0x1000 in the command register 0, the parameter ID number in

registers 2, 3 and the desired value in registers 4, 5.

No Error Codes

0x1001 (4097 decimal): WRITE FLOAT CMD. Set the value of a floating point

parameter. Write 0x1001 in the command register 0, the parameter ID number in

registers 2, 3 and the desired float value in registers 4, 5.

Failure 1

TooHigh -1 : value is above legal limit

TooLow -2 : value is below legal limit

ErrorNotFound 0x8000 : parameter id not found

All communications will be controlled by the Modbus functions. The Modbus
protocol will determine the function, address, size, and offset register for the
message. The command interface data will be within the data portion of the
message and will define the command to our unit.

Example 1: If you wish to read the span weight value you would:

1. Enter the Span parameter ID into registers 2 & 3. The Span ID is 0x0000 0201.

a.

Place 0x0000 into data register #2.

Advertising