Super Systems 9120 with TS User Manual

Page 16

Advertising
background image

SSi 9120 Touchscreen Interface

4586 – 9120 With Touch Screen Interface

Page 16 of 80


Use Input 3 as remote SP
This will allow the user to use input 3 as a remote setpoint. The options are: yes or no.

Control Input
This will allow the user to view the input that will act as a control T/C. This setting is fixed and cannot be
changed by the user.






Burnoff Setup
This menu option allows the user to
modify the settings that are associated
with the probe burnoff (menu option

Burnoff

).

Burnoff Time (sec)

The amount of time from the beginning of
the burnoff to the end of the burnoff
measured in seconds. The range is 0 to
600.

Burnoff Recovery Wait Time (sec)

The amount of time allotted to allow the
probe measurements to return to a stable,
accurate range after the burnoff is
complete. This is measured in seconds.
The control output is held until this time is
elapsed. The range is 0 to 300.


Burnoff Interval (min)

The amount of time between the beginning of one burnoff and the beginning of the next scheduled burnoff
measured in minutes. The range is 0 to 10080.

Burnoff Minimum Millivolts

The minimum measured millivolt tolerance of the probe required to start a burnoff. If the millivolts value is
exceeded

the burnoff will stop

. This is done to help maintain the life and the accuracy of your probe.

The range is 0 to 2000.

Burnoff Maximum Temperature
The maximum measured temperature allowed during a burnoff. If the temperature value is
exceeded

the burnoff will stop

. This is done to help maintain the life and the accuracy of your

probe. The range is 0 to 4000.