Alarm Setup

The 9120 controller can be configured to use
three different alarms. Each of the alarms
consists of an alarm setpoint, alarm type, alarm
hysteresis, smart alarm, ON delay time, and a 0
SP blocks alarm value. The alarms come from
the factory with a default configuration
dependent on the application but also can be
modified prior to shipment to your facility or in
the field by a supervisor.

Setpoint
This value is the setpoint for the alarm.
Clicking on this value will display an input box from which the user can select a new value. The
range is from –9999.00 to 9999.00.

Alarm Type
This value is the type of alarms used. Clicking on this value will display an input box with two (2)
drop-down lists from which the user can select a new value.
The values in the first (top) list box are:

PV 1 Value

PV 2 Value

PV 3 Value

Input 1 Value

Input 2 Value

Input 3 Value

PO1 Value

PO2 Value

PO3 Value


The values in the second (bottom) list box are:

Process High

Process Low

Band, Normally Open or Out of Band

Band, Normally Closed or In Band

Deviation, Normally Open or Outside Deviation

Deviation, Normally Closed or Within Deviation

Hysteresis
This value is the Hysteresis value. The Hysteresis is a set number that works with the alarm to
help control a motor or pump longer to reach a set amount to come back into band before it will
shut off motor or pump.

Example: Using quench oil as an example, suppose the SP is 200 ◦F. The alarm is set as a
deviation of +10 ◦F. At 210 ◦F, the alarm is active and the pump will run to cool the oil. With a