4586 – 9120 With Touch Screen Interface

Page 62 of 80


In the “Zero Input 1/Range X” section, enter the zero voltage and click on the Calibrate button.
This will calibrate the zero range.
In the “Span Input 1/Range X” section, enter the span voltage that you are sourcing in and click
on the Calibrate button. This will calibrate the span range.

Clicking on the Next -> button will display the third screen for the user calibration – Zero/Span
input 2. Clicking on the <- Back button will display the previous screen.
Calibrate the zero/span range for input 2 and click on the Next -> button to continue to the
fourth screen – Zero/Span for input 3. Clicking on the <- Back button will display the previous
screen.
Calibrate the zero/span range for input 3 and click on the Next -> button to continue to the fifth
screen – Zero/Span Output 1. Clicking on the <- Back button will display the previous screen.

To calibrate the zero/span range for
output 1, you must first attach your
measuring device, then select Prep for
Zero
. Let the unit output what it has set
for the zero measurement, then enter
what you are measuring coming out of the
terminals. Once entered select Calibrate
and let the procedure finish. This will be
the same for the Span output. Then click
on the Next -> button to continue to the
sixth screen – Zero/Span Output 2. Clicking on the <- Back button will display the previous
screen.
Calibrate the zero/span range for output 2 following the same procedure as before with output 1.
Clicking on the <- Back button will display the previous screen. This is the last screen for user
calibration. Click on the Done button to close the screen down, or return to the first screen for
cold junction calibration.

Full Calibration
The

Calibration

screen for the Full Calibration menu option is identical in function and layout to

the User Calibration’s

Calibration

screen. The only difference is the Full Calibration’s

Calibration

screen contains more screens. The user calibration will calibrate the following items:
Cold Junction
Zero/Span Input 0 (Input 1)/All 4 Ranges
Zero/Span Input 1 (Input 2)/All 4 Ranges
Zero/Span Input 2 (Input 3)/All 4 Ranges
Zero/Span Input 1 Range Jumper
Zero/Span Input 2 Range Jumper