Modbus, Rtu serial communications, Pda1044 digital input & output expansion module – Precision Digital PD6200 User Manual

Page 13

Advertising
background image

Model PD6200 Analog Input Rate/Totalizer

Instruction Manual

13

Modbus

®

RTU Serial Communications

SLAVE ID

1 – 247 (Meter address)

BAUD RATE

300 - 19,200 bps

TRANSMIT
TIME DELAY

Programmable between 0 and 199 ms
or transmitter always on for RS-422 communication

DATA

8 bit (1 start bit, 1 or 2 stop bits)

PARITY

Even, Odd, or None with 1 or 2 stop bits

BYTE-TO-BYTE
TIMEOUT

0.01 – 2.54 second

TURN AROUND
DELAY

Less than 2 ms (fixed)

Note: Refer to the P

RO

V

U

®

Modbus Register Tables located at www.predig.com

for details.

PDA1044 Digital Input & Output Expansion Module

CHANNELS

4 digital inputs & 4 digital outputs per module

SYSTEM

Up to 2 modules for a total of 8 inputs & 8 outputs

DIGITAL INPUT
LOGIC HIGH

3 to 5 VDC

DIGITAL INPUT
LOGIC LOW

0 to 1.25 VDC

DIGITAL OUTPUT
LOGIC HIGH

3.1 to 3.3 VDC

DIGITAL OUTPUT
LOGIC LOW

0 to 0.4 VDC

SOURCE
CURRENT

10 mA maximum output current

SINK
CURRENT

1.5 mA minimum input current

+5 V
TERMINAL

To be used as pull-up for digital inputs only
Connect normally open pushbuttons across +5 V & DI 1-4.