Model PD6200 Analog Input Rate/Totalizer

Instruction Manual

41

Error Message (Error)

An error message indicates that the calibration or scaling process was not
successful.
After the error message is displayed, the meter reverts to input 2 during
calibration or scaling and to input 1 during internal calibration, allowing
the appropriate input signal to be applied or programmed.
The error message might be caused by any of the following conditions:
1.

Input signal is not connected to the proper terminals or it is connected
backwards.

2. Wrong signal selection in Setup menu.
3. Minimum input span requirements not maintained.
4. Input 1 signal inadvertently applied to calibrate input 2.

Minimum Input Span

The minimum input span is the minimum difference between input 1 and
input 2 signals required to complete the calibration or scaling of the meter.

Input range

Input 1 & input 2 span

4-20 mA

0.15 mA

10 VDC

0.10 VDC