Model PD6200 Analog Input Rate/Totalizer

Instruction Manual

83

2. Press the Up arrow button to scroll to the Internal calibration menu

(ICAL) and press Enter.

3. The meter displays either current calibration (C CAL) or voltage cali-

bration (v CAL), according to the input setup. Press Enter to start
the calibration process.
Example of Internal Calibration for current input:

4. The meter displays low input current message (C lo). Apply the low

input signal and press Enter. The display flashes for a moment while
the meter is accepting the low input signal.

5. After the display stops flashing, a number is displayed with the left-

most digit brighter than the rest. The bright digit is the active digit
that can be changed by pressing the Up arrow button. Press the
Right arrow button to move to the next digit.

6. Set the display value to correspond to the input signal being cali-

brated, typically 4.000 mA.

7. The display moves to the high input calibration (C Hi). Apply the

high input signal and press Enter.

8. Set the display for the high input calibration, in the same way as it

was set for the low input calibration, typically 20.000 mA.

C CAL

ICAL

C Lo

C CAL

C Hi

C CAL

0

04.000

C Lo

0

20.000

C Hi

The display

f lashes while

sensing the

inputs

ICAL


The graphic above shows the calibration of the current input. The voltage
input is calibrated in a similar way.