Instruction Manual

62

Latching Relay (Lt-Clr)

Manual reset only after alarm condition has cleared

Condition

LED

Relay

Normal Off

Off

Alarm On

On

Ack (No effect)

On

On

Normal On

On

Ack Off

Off

In this application, the meter is set up for manual reset only after the
signal passes the reset point (alarm condition has cleared). Acknowledg-
ing the alarm while it is still present has no effect on either the LED or
the relay. When the alarm is acknowledged after it returns to the normal
state, the LED and the relay go off. Notice that the LED remains on,
even after the meter returns to the normal condition. This is because, for
latching relays, the alarm LED reflects the status of the relay, regardless
of the alarm condition.

Acknowledging Relays

There are two ways to acknowledge relays programmed for manual re-
set:

1. Via the programmable front panel function keys F1-F3 (Default:

F3 assigned to ACK)

2. Remotely via a normally open pushbutton wired across one of the

digital inputs and the +5 V terminals on the digital I/O modules.

When the ACK button or the assigned digital input is closed, all relays
programmed for manual reset are acknowledged.

+5

I1

I2

I3

I4

O1

O2

O3

O4

G

DO 1-4

GND

ACK

PDA1044 Digital I/O Module

1

2

3

4

5

6

7

8

9

10

DI 1-4

Figure 19: Acknowledge Relays w/Function Key or Digital Input