Model PD6200 Analog Input Rate/Totalizer

Instruction Manual

19

Transmitter Supply Voltage Selection (P+, P-)

All meters, including models equipped with the 12/24 VDC power
option, are shipped from the factory configured to provide 24 VDC
power for the transmitter or sensor.
If the transmitter requires 5 or 10 VDC excitation, the internal jumper
J4 must be configured accordingly.
To access the voltage selection jumper:

1. Remove all the connectors.
2. Unscrew the back cover.
3. Slide the back cover about 1 inch.
4. Configure the J4 jumper, located behind the input signal connector,

for the desired excitation voltage as shown.

MAIN BOARD

INPUT
SIGNAL

J4

5 V

10 V

24 V

J4 CONFIGURATION

Factory Default

P+

P-

mA+

COM

V+

Figure 5: Transmitter Supply Voltage Selection

Connections

All connections are made to removable screw terminal connectors
located at the rear of the meter.

!

Caution!

Use copper wire with 60°C or 60/75°C insulation
for all line voltage connections. Observe all safe-
ty regulations. Electrical wiring should be per-
formed in accordance with all applicable national,
state, and local codes to prevent damage to the
meter and ensure personnel safety.