Model PD6200 Analog Input Rate/Totalizer

Instruction Manual

47

Setting the Relay Operation (relay)

This menu is used to set up the operation of the relays.
CAUTION! During setup, the relays do not follow the input and they will

remain in the state found prior to entering the Relay menu.

1. Relay

assignment

a. Rate for low and high alarm
b. Total
c. Grand

total

2. Relay

action

a. Automatic reset only (non-latching)
b. Automatic + manual reset at any time (non-latching)
c.

Latching (manual reset only)

d. Latching with Clear (manual reset only after alarm condi-

tion has cleared)

e. Pump alternation control (automatic reset only)
f.

Sampling (the relay is activated for a user-specified time)

g. Off (relay state controlled by Interlock feature)

3. Set and reset points
4. Fail-safe

operation

a. On

(enabled)

b. Off

(disabled)

5. Time

delay

a. On delay (0-999.9 seconds)
b. Off delay (0-999.9 seconds)

6. Relay action for loss (break) of 4-20 mA input (ignore, on, off)