Precision Digital PD6200 User Manual

Page 80

Advertising
background image

Model PD6200 Analog Input Rate/Totalizer

Instruction Manual

80

Low-Flow Cutoff (CutofF)

The low-flow cutoff feature allows the meter to be programmed so that
the often-unsteady output from a differential pressure transmitter, at low
flow rates, always displays zero on the meter.
The cutoff value may be programmed from 0 to 999999. The meter will
display zero below the cutoff value. Programming the cutoff value to zero
disables the cutoff feature.

Analog Output Programming (AoutPr)

The Analog Output Programming menu is used to program the behavior
of the 4-20 mA output. The following parameters and functions are pro-
grammed in this menu:
1. Source: Source for generating the 4-20 mA output (e.g. PV)
2. Overrange: Analog output value with display in overrange condition
3. Underrange: Analog output value with display in underrange condition
4. Break: Analog output value when loop break is detected
5. Max: Maximum analog output value allowed regardless of input
6. Min: Minimum analog output value allowed regardless of input
7. Calibrate: Calibrate the internal 4-20 mA source reference used to

scale the 4-20 mA output

Analog Output Source

The source for generating the 4-20 mA output may be assigned to the
rate/process variable, total, grand total, maximum or minimum value
reached by the rate/process, or one of the set points, or the Modbus PV
input.

rate

Source

Source

AoutPr

Set Points

1 - 8

tot

Source

gtotal

Source

min

Source

max

Source

mbus

Source

Analog Output Calibration

To perform the analog output calibration it’s recommended to use a mil-
liamp meter with a resolution of at least 0.1 µA to measure the output
current. The values saved internally during this procedure are used for
scaling the 4-20 mA output in the Setup menu.