Model PD6200 Analog Input Rate/Totalizer

Instruction Manual

56

Rate Relay Sampling Operation

Set

Reset

Relay

LED

Input

Sample

Time

Sample

Time

Sample

Time

When the signal crosses the set point, the relay trips and the sample
time starts. After the sample time has elapsed, the relay resets. The
cycle repeats every time the set point is crossed, going up for high
alarms and going down for low alarms.
The sample time can be programmed between 0.1 and 5999.9 seconds.

Total Relay Sampling Operation

Preset = 100

100

Relay

LED

Total

200

300

Sample

Time

Sample

Time

Sample

Time

When the total reaches the preset, the relay trips and the sample time
starts. After the sample time has elapsed, the relay resets. The cycle
repeats every time the preset value is added to the total.