Process input – Precision Digital PD6200 User Manual

Page 9

Advertising
background image

Model PD6200 Analog Input Rate/Totalizer

Instruction Manual

9

NORMAL MODE
REJECTION

Greater than 60 dB at 50/60 Hz

ISOLATION

4 kV input/output-to-power line
500 V input-to-output or output-to-P+ supply

OVERVOLTAGE
CATEGORY

Installation Overvoltage Category II:
Local level with smaller transient overvoltages than Installa-
tion Overvoltage Category III.

ENVIRONMENTAL Operating temperature range: -40 to 65°C

Storage temperature range: -40 to 85°C
Relative humidity: 0 to 90% non-condensing

CONNECTIONS

Removable screw terminal blocks accept 12 to 22 AWG
wire, RJ45 for external relays, digital I/O, and serial com-
munication adapters.

ENCLOSURE

1/8 DIN, high impact plastic, UL 94V-0, color: black

MOUNTING

1/8 DIN panel cutout required:
3.622" x 1.772" (92 mm x 45 mm)
Two panel mounting bracket assemblies are provided.

TIGHTENING
TORQUE

Screw terminal connectors: 5 lb-in (0.56 Nm)

OVERALL
DIMENSIONS

4.68" x 2.45" x 5.64" (119 mm x 62 mm x 143 mm)
(W x H x D)

WEIGHT

9.5 oz (269 g)

WARRANTY

3 years parts & labor

Process Input

INPUTS

Field selectable:
0-20, 4-20 mA,

10 V (0-5, 1-5, 0-10 V), Modbus PV (Slave)

ACCURACY

±0.03% of calibrated span ±1 count,
square root & programmable exponent accuracy range:
10-100% of calibrated span

TEMPERATURE
DRIFT

0.005% of calibrated span/

C max from 0 to 65C ambient,

0.01% of calibrated span/

C max from -40 to 0C ambient

SIGNAL INPUT

CONDITIONING

Linear, square root, programmable exponent, or round
horizontal tank volume calculation

MULTI-POINT
LINEARIZATION

2 to 32 points

PROGRAMMA-
BLE EXPONENT

1.0001 to 2.9999

LOW-FLOW
CUTOFF

0-999999 (0 disables cutoff function)

Advertising
This manual is related to the following products: