Model PD6200 Analog Input Rate/Totalizer

Instruction Manual

60

Front Panel LEDs

The LEDs on the front panel provide status indication for the following:

LED Status

LED Status

1

Alarm 1

5

Alarm 5

2

Alarm 2

6

Alarm 6

3

Alarm 3

7

Alarm 7

4

Alarm 4

8

Alarm 8

The meter is supplied with four alarm points that include front panel
LEDs to indicate alarm conditions. This standard feature is particularly
useful for alarm applications that require visual-only indication. The LEDs
are controlled by the set and reset points programmed by the user.
When the display reaches a set point for a high or low alarm, the corres-
ponding alarm LED will turn on. When the display returns to the reset
point the LED will go off. The front panel LEDs respond differently for
latching and non-latching relays.
For non-latching relays, the LED is always off during normal condition
and always on during alarm condition, regardless of the state of the relay
(e.g. Relay acknowledged after alarm condition).
For latching relays, the alarm LEDs reflect the status of the relays, re-
gardless of the alarm condition. The following tables illustrate how the
alarm LEDs function in relation to the relays and the acknowledge button
(Default: F3 key assigned to ACK):

Latching and Non-Latching Relay Operation

The relays can be set up for latching (manual reset) or non-latching (au-
tomatic reset) operation.

Relay terminology for following tables

Terminology

Relay Condition

On Alarm

(Tripped)

Off Normal

(Reset)

Ack Acknowledged

The On and Off terminology does not refer to the status of the relay’s
coil, which depends on the fail-safe mode selected.

Warning!

In latching relay mode, latched relays will reset (un-
latch) when power is cycled.