Model PD6200 Analog Input Rate/Totalizer

Instruction Manual

64

Application #2: Pump Alternation Using Relays 3 & 4

1. Relays 1 and 2 are set up for low and high alarm indication.
2. Relays 3 and 4 are set up for pump alternation.

Set and Reset Point Programming

Relay

Set Point

Reset Point

Function

1 495

750

Controls

low

alarm

2

7500

6900

Controls high alarm

3

7000

900

Controls backup pump

4 6000 1000

Controls

main

pump

The following graphics provide a visual representation of a typical pump
alternation application with high and low alarm monitoring:

 Relay #4 turns the main pump on at 6000 gallons and turns it off

at 1000 gallons.

 With the Pump Alternation feature activated, the next time the

level reaches 6000 gallons, relay #3 transfers and starts the
backup pump.