as it hangs to the floor. Place excess cable out of the way in a neatly coiled loop.
Placing fasteners on the loop helps to maintain its shape.

CAUTION:

Do not let fiber-optic cable hang free from the connector. Do

not allow fastened loops of cable to dangle, which stresses the cable at
the fastening point.

CAUTION:

Avoid bending fiber-optic cable beyond its minimum bend

radius. An arc smaller than a few inches in diameter can damage the cable
and cause problems that are difficult to diagnose.

12.

Use one of the following methods to bring the DPC online:

Press and hold the corresponding DPC online button on the craft interface until the
green

OK

LED next to the button lights steadily, in about 5 seconds.

Issue the following CLI command:

user@host>

request chassis fpc slot slot-number online

For more information about the command, see the Junos OS Operational Mode
Commands.

CAUTION:

After the

OK

LED turns green, wait at least 30 seconds before

removing the DPC again, removing a DPC from a different slot, or inserting
a DPC in a different slot.

You can also verify that the DPC is functioning correctly by issuing the

show chassis fpc

and

show chassis fpc pic-status

commands.